Permit: T12PL00095

Parcel: 131121700


Addresses:

6102 E 31ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/23/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
01/20/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/19/2012 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TOTAL DEVELOPED LENGTH IS 60' PLUS NOT 38'
2) BTU DEMAND IS 185,000
3) PROVIDE 1' MINIMUM NEW PIPING, AND REVISE PLAN TO SHOW DRYER AND 1" LINE SIZE
4) WATER HEATER VENT REQUIRES 1" CLEARANCE AT ROOF AND SECREWS IN EACH JOINT
5) GAS METER IS PINNED AND TAGGED OFF