Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2012 | FIRE - FINAL | Approved | ||
| 09/27/2012 | FIRE - FINAL | Denied | 1. Fix emergency lighting above entry door. 2. Mount fire extinguisher with supplied bracket on wall. 3. Correct sprinkler coverage (to the left after entering business) sprinkler heads too close together.. approx 4' appart. 4. Replace/repair holes in ceiling and wallboard throughout. |