Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12OT01174
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2012 | FIRE - FINAL | Approved | ||
08/10/2012 | FIRE - FINAL | Denied | 1. NEED APPROVED PLANS ON SITE. 2. NEED TO FIX THE MAJORITY OF EMERGENCY LIGHTS THEY FAILED TO WORK WHEN BREAKER WAS SHUT OFF. 3. NEED TO REMOVE KEYED LOCK ON THREE OF THE FAR NORTH EXIT DOORS. 4. BUILDING HAS SMOKE DETECTORS HAVE THE BEEN TESTED OR APPROVED. |