Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12OT01129
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2012 | FIRE - FINAL | Approved | ||
08/08/2012 | FIRE - FINAL | Not ready for Inspection | 1. everything is corrected. 2. still need annual sprinkler report and the five year check valve paper work. |
|
08/06/2012 | FIRE - FINAL | Denied | 1. Need annual fire inspection done. 2. Need a 5 year check valve inspection done. 3. Need to add sprinkler coverage in closet in back room or remove top. 4. Front door has panic hardware on door and double cylinder keyed dead bolt lock can not have both on door, need to remove one of the locks from the door. If you remove the panic hardware from door then you will need to label above the door inside the following :"THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 1 inch high lettering. |