Permit: T12OT01129

Parcel: 13312006M

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12OT01129

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2012 FIRE - FINAL Approved
08/08/2012 FIRE - FINAL Not ready for Inspection 1. everything is corrected.
2. still need annual sprinkler report and the five year check valve paper work.
08/06/2012 FIRE - FINAL Denied 1. Need annual fire inspection done.
2. Need a 5 year check valve inspection done.
3. Need to add sprinkler coverage in closet in back room or remove top.
4. Front door has panic hardware on door and double cylinder keyed dead bolt lock can not have both on door, need to remove one of the locks from the door. If you remove the panic hardware from door then you will need to label above the door inside the following :"THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 1 inch high lettering.