Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12OT00963

Parcel: 11520005D


Addresses:

1953 W GRANT RD


Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T12OT00963

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2012 SIGN SITE REVIEW Approved
09/06/2012 SIGN SITE REVIEW Partial Approval Move hole positions 2' south to meet setback. Field check for setback and footer depth to occur 9/7 a.m. Ok to release permit - contractor contacted will revise hole location.
09/05/2012 SIGN SITE REVIEW Partial Approval All site plans, construction details and photos received showing vegetation is non-native where the sign is proposed to be installed. Setback inspection to occur 9/6/12.
08/28/2012 SIGN SITE REVIEW Partial Approval Contractor provided revised drawings and construction details. Waiting for photos to show proposed sign position and vegetation in the area affected by the sign's proposed installation.
06/27/2012 SIGN SITE REVIEW Denied The submitted package did not include enough information to review the proposal completely, however, staff noted as a courtesy some issues that should be addressed with the additional requested information.

Per 3-18.B & B.3. A scaled site plan is required for the review of a proposed freestanding sign. The site plan needs to show property lines, street curbs, linear street frontage dimensioned, sight visibility triangles, driveways, site layout of buildings and setback from the street curb to the leading edge of the sign.

Per 3-18.B.4. Please provide construction drawings showing the material the sign is made of and how assembled/supported. Provide drawing of footer depth and width. Dimension the sign on the photo and the construction detail. Measure height from adjacent elevation at the roadway.

Per 3-60.A.4. a 20' setback from the face of street curb to the leading edge of the sign is required. The photo layout in the submitted package does not have a dimension, but it appears the sign will be too close to the street.

Per definition of a monument sign - provide a pole cover on both poles - or the sign would have to be mounted directly on a foundation.

For questions on this review, contact Heather.Thrall@tucsonaz.gov or 837-4975.