Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T12OT00324
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2012 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SIGN IS NO LISTED, HAVE NRTL EVALUATE OR ADD SHOP TO PERMIT 2) NEED CURRENT MARKING LABEL 600.4 3) VERIFY SIGN CIRCUIT 600.5 & LABEL CORRECTLY 4) SIGN BODY INTERIOR HAS NON CODE COMPLIANT ITEM THAT NEED REPAIR 5) USE APPROVED SCREWS FOR GROUNDING 250.8 6) GROUND ALL JUNCTION BOXES 250.? |
|
| 04/02/2012 | SIGN ELECTRIC | Cancelled | CANCELLED PER RAY OF SUNRAY SIGNS #940-2466 | |
| 04/02/2012 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* |