Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T12ME00108
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2013 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/28/2013 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | 1. LINE SET INSUALTION TO BE COATED FOR U.V PROTECTION 2. UNIT SUPPORTS NOT PROPERLY INSTALLED 3. DO NOT DOUBLE LUG AT CONDENSOR DISCONNECT 4. PROVIDE SERVICE OUTLET ON ROOF 5. PROVIDE MINIMUM CLEARANCE ON BVENT |
|
| 02/07/2013 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) B-VENT DOES NOT HAVE MINIMUM CLEARANCE FROM COMBUSTIBLES. 2) HIGH COMBUSTION AIR VENT MUST BE A MIN. OF 100 SQ INCH 3) ALL P.V.C PIPE IS TO HAVE JOINTS AND FITTINGS PRIMORED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR 4) PROVIDE ACCESS TO FILTER RACK, UNABLET TO REMOVE FILTER WITH OUT DAMAGING IT. 5) SINGLE WALL FLUE TO HANG 6" CLEARANCE FROM COMBUSTIBLE MATERIAL (PIPE INSULATION) 6) POWER CORD AT FURNACE NEET PROPERLY INSTALLED. 7) SUPPLY DUCT NOT SEALED 8) PROVIDE PERMIT FOR WATER HEATER INSTALL 9) PROVIDE ROOF ACCESS TO CONTINUE INSPECTION |