Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2013 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 01/25/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
termiate condensate to ann approved location block and clamp condensate every 4' extend sewer vents min 2' above fresh air intakes |