Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T12ME00037
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/07/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/01/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OUTDOOR LINE SET TO BE COATED FOR U.V. PROTECTION 2) SEAL TITE TO BE SUPPORTED UP OFF OF GROUND 3) PROVIDE APPROVED FUSES (DO NOT WRITE ON FUSES) 4) PLUG OPEN HOLE IN DISCONNECT 5) PROVIDE SECONDARY DRAIN (EZ-TRAP) 6) TIE IN CONDENSATE PUMP SWITCH 7) INDOOR DATA PLATE NOT IDENTIFIED (HEAT STRIP) |