Permit: T12ME00026

Parcel: 131090910


Addresses:

5711 E 26TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/02/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/17/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL DUCT WORK ON ROOF TO HAVE MINIMUM 2" LINER
2) ALL JOINTS ARE TO BE SEALED
3) REMOVE ROOF COATING FROM AC SICONNECTS
4)1" LINED DUCT TO REMAIN ON SITE UNITL FINAL INSPECTION IS SIGNED OFF
5) THIS IS A NEW INSTALLATION, PROVIDE ROOF LOAD CALCS FOR EACH UNIT. REVISE PERMIT