Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/19/2012 | ELECTRIC - RECONNECT | Not ready for Inspection | 1. ALL ROMEX IN LAUNDRY ROOM BELOW 8' TO BE PROTECTED (COVERED) 2. ROMEX ON BACK PORCH CODE SEE NOTE1 3. ROMEX ON CARPORT NOT TO CODE SEE NOTE 1 4. THIS IS AN UNGROUNDED SYSTEM, PROVIDE UFER GROUNDING ELECTRODE OR OTHER APPREHEND MEANS OF GROUNDING OR REPLACE OUTLETS WITH UNGROUNDED OUTLETS 5. ALL BEDROOMS AND HALL LEADING TO BEDROOMS ARE TO HVE SMOKE ALARMS |