Permit: T12EL00673

Parcel: 135082300


Addresses:

7352 E EASTVIEW DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/03/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/01/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER INSULATION IS NOT THE RIGHT TYPE
2. GROUNDRODS 2 MISSING
3. GUTTER BOX NOT BONDED, GROUND USED AS NEUTRAL. RUN SEPERATE NEUTRAL WIRE FROM PANEL TO GUTTER
4. ROMEX TO EMT SUBJECT TO PHYSICAL DAMAGE FROM SERVICE PANEL AND GUTTER
5. GROUNDING ELECTRIC TO BE STRAPED TO WALL