Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/01/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER INSULATION IS NOT THE RIGHT TYPE 2. GROUNDRODS 2 MISSING 3. GUTTER BOX NOT BONDED, GROUND USED AS NEUTRAL. RUN SEPERATE NEUTRAL WIRE FROM PANEL TO GUTTER 4. ROMEX TO EMT SUBJECT TO PHYSICAL DAMAGE FROM SERVICE PANEL AND GUTTER 5. GROUNDING ELECTRIC TO BE STRAPED TO WALL |