Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2017 | ELECTRIC - RECONNECT | Approved | ||
| 01/17/2013 | ELECTRIC - RECONNECT | Partial Approval | UNIT 1 WIRING AT CARPORT LIGHT NOT PER CODE. GROUNDED RECEPTACLES STILL ON NON GROUNDED CIRCUITS WIRING IN SUB PANEL CLOSET NOT TO CODE. FILL UNUSED KNOCKOUTS | |
| 07/31/2012 | ELECTRIC - RECONNECT | Denied | 1) WIRING IN ROOM WITH SUB PANEL NON CODE COMPLIANT INCLUDING SUB PANEL 2) BASE BOARD HEATER DETACHED FROM WALL 3) INSTALL SMOKE DETECTORS AS PER INSTURCTIONS 4) MISSING COVER FOR FUSE SUB PANEL AND FUSES 5) GROUNDED RECEPTACLES ON NON GROUNDED CIRCUITS 6) SUPPORT CONDUITS AT MAIN PANEL FILL UNUSED OPENINGS 7) LABEL UNITS 8) PLEASE VERIFY QUALIFIED PERSON DOING WORK |