Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/13/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/13/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1. SECURE PANEL TO WALL PER CODE 2. SECURE RISER CLAMPS TO CODE 3. SECURE #4 TO WALL PER CODE 4. SEAL OPENINGS DEAD FRONT 5. METAL ADDRESS TAG NEXT DENIAL WILL RESULT IN A RE-FEE |
|
| 06/12/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/12/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1. USE APPROVED SUPPORT BELOW ROOF OVERHANG 2. INSTALL EQUIP GROUND TO J-BOX. DO NOT USE NEUTRAL WIRE |
|
| 06/10/2013 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/05/2012 | ELECTRIC - SERVICE UPGRADE | Cancelled | CANCELLED PER HOMEOWNER PRICILLA #401-0063 | |
| 03/05/2012 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) INSTALLATION NOT COMPLETED TO THE POING OF INSPECTION, CONTACT A QUALIFIED ELECTRICIAN TO COMPLETE WOKR |