Permit: T12EL00346

Parcel: 10709066D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/15/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/14/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH FILLING HOLES IN PANEL AND BREAKER SPOTS
2) CIRCUIT PANEL FOR 110 V OFF OF 30 AMP CORDS
3) USE BREAKERS FOR MANUFACTURE GE
02/10/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE CABLES TO PANEL
2) FILL UNUSED OPENINGS IN PANEL
3) PLUG IS 110V 30 AMP-PANEL IS BEING WIRED 220V 50 AMP NOT MATCHING
4) COOLER SWITCH NOT IN ELECTRICAL BOX AND CORD WIRED NOT CODE COMPLIANT
5) SMOKE DETECTORS