Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) NOTE: A NEW PERMIT WILL NEED TO BE OBTAINED AT TIME OF CONNECTION TO SPARE CIRCUITS |
|
| 02/14/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CANNOT TAPE A GREEN CONDUCTOR WHATE 200.6 AND 250.119, NEEDS TO BE WHITE ENTIRE LENGTH 2) FINISH PREVIOUS ITEMS |
|
| 02/13/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE VERIFY PERMIT FOR NEW WORK TO INTERIOR-NEW DRYWALL AND WIRING 2) MAINTAIN SAFE WORKING SPACE AT FRONT OF SERVICE 3) CORRECTLY IDENTIFY GROUNDED CONDUCTOR-NOT A GROUNDING CONDUCTOR 4) BOND JUNCTION BOX 5) WHAT ARE SPARK BREAKERS FOR ? 1-30 A AND 2-20 A 6) OK GROUND RODS |