Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/15/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH #3 AND 8 PREVIOUS ITEMS 2) FILL UNUSED OPENING IN BOX WHERE WIRE REMOVED (DINNING) |
|
| 02/03/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING WEATHER PROOF COVER IRRIGATION RECEPT 2) SECURE AND PROTECT UF CABLES BACK OF HOUSE 3) MAINTAIN WORKING SPACE AT SERVICE 4) BREAKERS AT GARAGE SUB PANEL NOT TO MANUFACTURE 5) NEED SMOKE DETECTOR IN HALL 6) INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS 7) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS 8) CLOSET FIXTURES NOT CODE COMPLIANT 9) BATHROOM RECEPT TO BE GFCI PROTECTED 10) REPLACE KITCHEN RECEPTS TO BE GFCI PROTECTED 11) ? LIGHT NOT TO BE ZIP CORD-INSTALL USING APPROVED METHODS |