Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12EL00274

Parcel: 117022940


Addresses:

927 N JACOBUS AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T12EL00274

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/28/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH CONDUIT STRAPS
2) RECEPT COVERS TO BE WEATHER PROOF WHETHER PLUGGED INTO OR NOT
3) FINISH #3 LAST INSPECTION
02/03/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTDOOR BOX NOT WEATHER RESISTANT
2) CONDUIT FITTING NOT FOR OUTDOOR USAGE-NOT WEATHER RESISTANCE
3) MAINTAIN WORKING SPACE AT SERVICE
4) EXPOSED NM CABLE ON EXTERIOR
5) GROUNDED RECEPTS ON NON GROUNDED WIRING
6) EXPOSED NM CABLE SIN CUPBOARDS
7) PLEASE VERIFY IF BACK BLDGS ARE POWERED OFF OF THIS UNIT-NUMEROUS CODE COMPLIANT ISSUES ON THOSE BLDGS