Permit: T12EL00272

Parcel: 106021820


Addresses:

156 W PASTIME RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/08/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/02/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPENINGS BACK OF PANEL AND PROTECT CONDUCTORS
2) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS AND CANNOT TRIM CONDUCTORS
3) SECURE PVC CONDUIT TO WALL OR STRUCTURE
4) FINISH SMOKE DETECTOR BEDROOM AND RECEPTS AT PANEL
03/01/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/29/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/02/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSED WIRING STORAGE SHED INTERIOR AND EXTERIOR
2) FILL UNUSED OPENING IN PANEL COVER AND BOTTOM OF PANEL
3) EXPOSED CABLE WIRES FOR OUTLET AND MAKE WEATHER RESISTANT (SIDE OF WINDOW) AND LIGHTS
4) FIXTURE NEEDS ELECTRICAL BOX
5) LOOSE WIRING AND BOXES UNDER SINK
6) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS
7) NEED SMOKE DETECTORS IN BEDROOMS AND MISSING IN HALL
8) CEILING FAN NOT TO BE CORD AND PLUG CONNECTED