Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 02/28/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) GATE LOCKED, NO PERSON ON SITE AND NO MESSAGE 2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO ACCESS |
|
| 02/21/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BOX EXTENDERS FOR RECEPTS, SWITCHES WHERE ADDING DRYWALL OVER EXISTING WALLS AND CEILING, LEAVE LIGHT FIXTURES PARTIALLY FASTENED TO CEILING FOR INSPECTION, OR HAVE ELECTRICIAN ON SITE TO REMOVE AND REPLACE 2) SMOKE DETECTORS REQUIRED IN HALLWAY AND BEDROOMS 3) ROMEX (STORAGE) BELOW 8' TO BE PHYSICALLY PROTECTED 4) USE QUALIFIED OR LICENSED ELECTRICIAN |
|
| 02/02/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) CALLED PER REQUEST-UNIT LOCKED AND NO RETURN CALL 2) RESCHEDULE INSPECTION 3) LEFT MSG. VIA VOICE MAIL |
|
| 01/27/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) HOUSE LOCKED, COULD NOT RETRIEVE MSG. 2) RESCHEDULE INSPECTION AND LEAVE MSG. FOR INSPECTOR |