Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2012 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 02/08/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POOL WIRING FOR EQUIP NOT TO CODE, LAYING ON GROUND 2. SPLICED GBL MUST BE IRREVERIBLE, CRIMP OR CAD WELD 3. BACK BOARD NEEDS TO BE REPLACED BEHIND SERVICE EQUIP. 4. CAP OFF EXPOSED WIRING FOR LIGHT FIXTURE ETC. 5. SMOKE DETECTORS REQUIRED IN BEDROOMS 6. OVERHEAD UTILITY DROP NEEDS TO BE 22 FT FROM WATER IN POOL PER 680.8 NEC. 7. BOND WATER + GAS 8. OUTSIDE 110V RECEPTICLES SHOULD BE GFI PROTECTED |