Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12EL00193
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/25/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPIRED PERMIT FOR SERVICE UPGRADE, REOPEN PERMIT AND COMPLETE WORK-11/29/05 #T05EL02305 2) REMOVE OLD METER BASE, PLUG HOLE IN SUB PANEL ISOLATE GROUNDS AND NEUTRALS IN SUB PANEL. USE APPROVED J-BOX IN LIEU OF SUB PANEL 3) GROUND NEW SERVICE PER CODE-2 GROUND RODS 6' APART, BOND WATER & GAS AND NO TEP SEAL ON METER BASE ? 250 NEC 4) OUTSIDE RECEPT SHOULD BE GFI PROTECTED 5) OVERHEAD UTILITY DROP TO LOW ACROSS PARKING LOT-SHOULD BE 18" ABOVE GRADE PER 230.B4 |