Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12EL00168
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/22/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTES 2 & 4 FROM PREVIOUS |
|
01/23/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LEFT MSG. 9:50 AM 2) POST BLDG NUMBERS 3) PROVIDE 36" CLEARANCE IN FRONT OF SERVICE PANEL 4) LABEL CIRCUITS SUB PANEL 5) GROUNDED OUTLETS ON UNGROUNDED SYSTEM. RETURN TO ORIGINAL OUTLETS OR GFCI PROTECT HEAD OF CIRCUIT 6) SECURE RISER TO CODE |