Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 01/11/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE 1/4" BOLTS IN WALL FOR RISER SUPPORT 2) NO PENETRATION OR LOAD CONDUCTORS THRU TOP OF ENCLOSURE-SEE NOTES ON PANEL INSTRUCTION (DOOR PANEL) 110.3 NEC 3) OK GROUNDING 4) RECEPT AT BOTTOM OF PANEL NOT SUPPORTED 5) PROVIDE LADDER FOR ROOF INSPECTION |