Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL INSPECTION AFTER TEP TIE IN |
|
| 01/11/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE LISTED RISER CONDUIT BRACE, HOMEMADE OUT OF SMASHED EMT NOT APPROVED 110.3 NEC 2) SERVICE CANNOT BE OVER OR ABOVE GAS REGULATOR 110.26 NEC 3) MUST HAVE 36" IN FRONT AND 30" HORIZONTAL ABOVE AND BELOW EQUIP. |