Permit: T12EL00037

Parcel: 107081970

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/11/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/06/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED SMOKE DETECTORS BEDROOMS AND HALL
2) BROKEN RECEPT
3) BACK STORAGE:
A) STAPE NM CABLES 8" + 8'
B) FAN BOX APPEARS NOT TO BE FAN RATED
C) ROOM MAY HAVE BEEN CONSTRUCTED WITHOUT PERMITS
4) DISCONNECT POWER TO BACK BLDG OR RE-WIRE WITH PERMIT
5) ZIP CORD WIRING NOT AN ALLOWED METHOD
6) SUB PANEL IS AN UNGROUNDED SYSTEM-WIRING TAKEN BACK, PARTS ARE GROUNDED-ALSO IN CLOSET