Case: T12DV11328

Parcel: 130071910


Addresses:

3814 E 25TH ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
12/28/2012 INSP - INITIAL CODE ENFORCMENT Approved INSPECTOR VALDEZ CONDEMENED HOME DUE TO FAULTY ELECTRICAL. ON SITE INSPECTION; THE TWO BEDROOMS, LIVING ROOM AND A BATHROOM HAVE NO POWER TO THE RECEPTACLES AND LIGHTS. I INSPECTED THE INTERIOR SUB PANEL AND IT'S ENERGIZED BUT NO POWER TO THE ROOMS. I INSPECTED THE MAIN DISCONNECT AND THE ELECTRODE GROUNDING CONDUCTOR HAS BEEN CUT. THERE IS ALSO ANOTHER PANEL BOARD BELOW THE MAIN DISCONNECT WITH NON METALLIC SHEATHED CABLE RUNNING TO A JUNCTION BOX JUST HANGING OVER THE PORCH AREA. THE TENANTS STATE THE LIGHTS FLICKER OFF AND ON SOMETIMES. SCHEDULE A 10 DAY FOLLOW UP INSPECTION. PHOTOS IN SIRE,