Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T12DV06957
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2012 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE, MET WITH TFD CAPTAIN, WHO MENTIONED FIRE STARTED IN ROOM ADDITION OUTSIDE THE TRAILER. ADDITION WAS JUST OFF THE FRONT PORCH WITH A DOOR FROM THE TRAILER TO THE ADDITION ON THE SOUTH SIDE OF ADDITION, AND A DOOR ON THE WEST SIDE OF ADDITION WHICH WAS JUST A PIECE OF PLYWOOD ON HINGES. TENANT MELLISA BELTRAN MENTIONED SHE HAS ONLY BEEN THERE SINCE JUNE AND HAD BEEN USING THE BEDROOM FOR HER SON. THE ADDION HAD NO POWER AND SHE PLANNED ON FIXING IT UP. THERE WAS WIRING TO EACH OUTLET BOX BUT HAD NOT BEEN COMPLETED. MS. BELTRAN WAS RUNNING POWER FROM AN EXTENSION CORD FROM THE TRAILER TO THE ADDITION AND POWERED A LAMP AND THE COOLER. LAMP WAS KNOCKED OVER ONTO THE CLOTHES PILE WHICH STARTED THE FIRE. TFD HAD REMOVED DRYWALL AND OPENED UP THE WALLS AND CEILING REVEALING ILLEGAL SPLICES IN BOTH AREAS. SPLICES HAD BEEN BURNED BEFORE. ADDITION WAS 2X4 FRAME/ SIDING, 2X4 CEILING JOIST 24 INCH O.C. 1/2 INCH DRYWALL AND LEDGER CONNECTED TO THE TRAILER. FIRE WAS LIMITED TO THE ADDITION, DID NOT AFFECT THE TRAILER IN ANY WAY. FIRE LIMITED TO CLOTHING, A DRESSER, AND A CHAIR. REMOVED EXTENTION CORD RUNNING FROM THE TRAILER. ADDITION APPEARS TO BE AN ILLEGAL ADDITION. WILL ISSUE NOV FOR THE ILLEGAL ADDITION. |