Case: T12DV05889

Parcel: 138201350


Addresses:

7170 S SUSANA DR

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
07/20/2012 INSP - INITIAL CODE ENFORCMENT Approved Went to the property and no one home. Left a card on the security door and will wait for a call. Did try and call the phone number listed for the tenant and left a message. RV.
07/20/2012 INSP - INITIAL CODE ENFORCMENT Approved The tenant called and is back at the house and will meet a the property. Did an inspection and found no smoke detectors, water heater storage room has no combustible air releif openings in the door or walls, security window guards have no break-a-ways on the bedroom windows and some were pinned shut, the break-a-ways have pins that go through the wall and are not connected and able to push open if required with removing a tap in nail to open on window in the front bedroom, master bedroom shower has a drain cover not secured, electrical outlets loose or not secured properly, kitchen and bathroom outlets not GFCI, vents are missing or loose through out for the cooler, roof leaks, hall bathroom tub is plugging up and exhaust fan making noise of rattling, cooler not secured properly and weighted with red bricks, security doors not locking properly and have double key deadbolts. Will do N.O.V. RV.