Case: T12DV03567

Parcel: 137070300


Addresses:

5125 S 12TH AV

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
04/10/2014 INSP - FOLLOW UP CODE ENFORCE Approved THE BUSINESS DID CLOSE BUT THE PERMIT T13CM05899 IS FINAL FOR SERVICE UPGRADE 300 AMP PER CASE- T12DV03567 CLOSE CASE
10/14/2013 INSP - FOLLOW UP CODE ENFORCE Approved T13CM05899 SERVICE UPGRADE 300 AMP -
PERMIT EXPIRES ON 03/31/2014
09/03/2013 INSP - FOLLOW UP CODE ENFORCE Approved EXTENSION GRANTED DUE TO PE WAS HIRED SEE COND NOTES
07/17/2013 INSP - FOLLOW UP CODE ENFORCE Approved A NEW INSPECTION WAS CONDUCTED DUE TO NEW COMPLAINT, ONSITE INSPECTION RESULTS

1. WORKING CLEARANCE FOR MAIN DISCONNECT NOT TO CODE, THERE IS EQUIPMENT BLOCKING ACCESS.

2. IDENTIFICATION REQUIRED; NO LABELING FOR SERVICE EQUIPMENT AND THE INTERIOR PANELS TO INCLUDE ALL CIRCUITS.

3. NEW CONDUIT INSTALL REAR OF BUILDING UNDER MAIN SERVICE EQUIPMENT WITH INTERIOR FITTINGS. UNKNOWN LOCATION?

4. FILL USED OPENINGS IN THE SUB PANEL AND INTERIOR JUNCTION BOXES.

5. EXPOSED BLACK WIRE FROM INTERIOR JUNCTION BOX TO THE REACH IN COOLER.

6. INTERIOR PANEL A HAS GREEN GROUND WIRE CONNECTED TO A NEUTRAL WHITE WIRE.

7. WRONG TYPE OF BREAKER INSTALLED AT MAIN DISCONNECT, REQUIRES A T TYPE BREAKER.

8. OUTDOOR LIGHTING HAS CONDUIT WITH INTERIOR FITTINGS

9. RECEPTACLE BOX IN THE EXTERIOR HAS JUMPER WIRE FROM ADJACENT BOX.

10. MISSING COVER PLATES TO EXTERIOR RECEPTACLE BOXES

11. INTERIOR CONDUIT IS LOOSE

12. NEW A/C DISCONNECT, NO PERMITS

13. NEW ELECTRICAL WATER INSTALLED NO PERMIT

NEW NOTICE OF VIOLATION WILL BE ISSUED. OWNER HAS CONTACTED NEW CONTRACTOR SABINO ELECTRIC, WILL SCHEDULE MEETING WITH CONTRACTOR NEXT WEEK.
07/02/2013 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT WAS RENEWED EXPIRES 2-14-2014
06/17/2013 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT IS EXPIRED
11/30/2012 INSP - FOLLOW UP CODE ENFORCE Approved Permit renewed T12CM02860, schedule follow up inspection for 05-26-2013
11/26/2012 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T12CM02860 HAS EXPIRED SPOKE TO OWNER THIS MORNING AND ASK HIM TO REACTIVE THE PERMIT AND CALL FOR INSPECTION.
06/04/2012 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T12CM02860 IN ISSUED STATUS FOR One circuit for freezer (220 volt), one circuit for reach in cooler. PERMIT EXPIRES ON 11/17/2012, SCHEDULE A FOLLOW INSPECTION FOR 11-17 2012