Case: T12DV02443

Parcel: 11202033P


Addresses:

2000 E ROGER RD I


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T12DV02443

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2013 INSP - FOLLOW UP CODE ENFORCE Approved SEE COND.
11/13/2012 INSP - FOLLOW UP CODE ENFORCE Approved RESEARCH:
P.P. SHOWS SEVERAL PERMITS HAVE BEEN EXTENDED TO 4/29/2013.
T12CM02434---T12CM02433---T12CM02432---T12CM02431---T12CM02430---T12CM02428---T12CM02430---T12CM02431---T12CM02432---T12CM02433---T12CM02434---T12CM02428--
PERMIT T12CM02426 EXPIRES 1/14/2013
PERMITS:T12CM02429---T12CM02425 FINALED, COMPLIANT.
FOLLOW UP 1/15/2013
07/10/2012 INSP - FOLLOW UP CODE ENFORCE Approved OFFICE FOLLOW UP:
RESEARCH:
PROPERTY UNDER SEVERAL ACTIVE PERMITS.
1ST EXPIRATION DATE 10/17/2012
FOLLOW UP 10/17/2012
05/11/2012 INSP - FOLLOW UP CODE ENFORCE Approved OFFICE FOLLOW UP:
RESEARCH:
P.P. SHOWS SEVERAL PERMITS (9) FOR A/C REPLACEMENT AND EMERGENCY DISCONNECT REPAIRS/REPLACEMENT HAS BEEN ISSUED.
FOLLOW UP 60 DAYS.
04/12/2012 INSP - FOLLOW UP CODE ENFORCE Approved SCHEDULED INSP.
VISITED SITE:
WENT ON ROOF TOP W/ VISITING MAINT. SUPERVISOR. NOEL.
IST INSP. (4/4/12) ON ROOF TOP WAS FOR VENT PIPES.
UPON THIS INSP. WAS VISIBLE HAZARDOUS CONDITION EXISTED ON EMERGENCY DISCONNECTS.
DID GO OVER ISSUES WITH MANAGER AND REGIONAL MANAGER.
NEED TO SCHEDULE A MORE COMPLETE INSP. ON ELECTRICAL ISSUES.
SCHEDULED 4/12/12.
UPON THIS INSP. FOUND EVEN WORST CONDITIONS THAN EXPECTED.
EMERGENCY DISCONNECTS LAYING OPEN FACED ON ROOF TOP, RUSTED, HOLDING WATER, WIRING DETERIORATED FROM EXTERIOR ELEMENTS, CRACKED, OPEN CONTACT.
SOME DISCONNECTS HAVE BEEN BY PASSED, WIRING UNIT DIRECT. CONTACTORS RUSTED, CAPACITORS RUSTED ALL OPEN TO EXTERIOR ELEMENTS. HAZARDOUS THIS IS ON MOST UNITS ON ROOF TOPS.
HIGH POTENTIAL OF FIRE (ELECTRICAL)
HIGH POTENTIAL OF SHOCKS OR EVEN WORSE. IF WATER PUDDLES AND IS ENERGIZED THE WHOLE WATER PUDDLE IS ENERGIZED AS MUCH AS 240 VOLTS. EXPECTING RAIN THIS WEEK-END. UNITS, BOXES, ROOF TOP CAN BE ELECTRICALLY ENERGIZED.
SEE COND.