Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM08216

Parcel: 138190750


Addresses:

6742 S MARTIN LN


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T12CM08216

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/15/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
OWNER TO CHANGE TO CORRECT ADDRESS ON PERMIT. 2 GROUND RODS REQUIRED 6' MIN APART, STEEL CONDUIT USED FOR #4 GROUND MUST HAVE BOND BUSHINGS ON END. NO ADDRESS LABEL ON SERVICE. BOND WATER AND GAS PIPING. INSTALL ROOF JACK