Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/01/2013 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/01/2013 | BUILDING - FINAL | Partial Approval | TERMINATE CONDENSATE TO THE DIRT. BLOCK & CLAMP PVC EVERY 4'. SLOPE PVC MIN 1/8" PER FT. USE PURPLE PRIMER ON ALL FITTINGS PRIOR TO GLUE. REPAIR LOOSE WIRE STRANDS IN DISCONNECT. TAPE WHITE WIRE WITH GREEN TAPE AT DISCONNECT & BREAKER T13CM03896 - APPROVED (04035 & 04090) |