Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T12CM08199
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/12/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/12/2013 | BUILDING - FINAL | Not ready for Inspection | 1. PROVIDE AIR BALANCE AND STERILIZATION REPORTS 2. CONDENSATE DRAIN UNDERSINK IS KINKED 3. PROVIDE MIXING VALVE AT WATER HEATER AND INSULATE PIPE 4. WATER HEATER POWER NEEDS BOX 5. NEED TO INSPECT ROOFTOP 6. BATHROOM EXHAUST TO BE INTERLOCKED OR ON TIMECLOCK |