Permit: T12CM08199

Parcel: 129024560

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM08199

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2013 BUILDING - FINAL Approved IVRS - Inspection :*
07/12/2013 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
07/12/2013 BUILDING - FINAL Not ready for Inspection 1. PROVIDE AIR BALANCE AND STERILIZATION REPORTS
2. CONDENSATE DRAIN UNDERSINK IS KINKED
3. PROVIDE MIXING VALVE AT WATER HEATER AND INSULATE PIPE
4. WATER HEATER POWER NEEDS BOX
5. NEED TO INSPECT ROOFTOP
6. BATHROOM EXHAUST TO BE INTERLOCKED OR ON TIMECLOCK