Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM08122
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2013 | FIRE - FINAL | Approved | ||
02/22/2013 | FIRE - FINAL | Denied | Call only when finished with remodel. Contractor called for sprinkler final under his permit T12CM08122, Kazal fire needs to pay for there permit T13BU00178. I did a sprinkler inspection for final and found sprinkler coverage not adequate on sales floor; sprinkler heads are 8' 11" off wall to far needs to be 7' 6" off wall need to correct coverage. |