Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/18/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/10/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/26/2013 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/23/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/23/2013 ELECTRIC - FINAL Denied 1. INSTALL BUSHINGS AT CONDUIT ENDS INTO SERVICE CABINET
2. PLANS CALL FOR 600 MCM AC SECONDARYS
3. VERIFY UNDERGROUND CONDUIT APP
4. LETTER OF TORQUE FOR SES
5. BOND WATER/GAS PIPING