Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/10/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/26/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/23/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|