Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/24/2013 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) ROMEX TO BE CLAMPED WITHIN 12" OF JUNCTION BOX, PROVIDE K.O. CLOAMPS NOT PLASTIC BUSHINGS. 2) JUNCTION BOX TOO SMALL FOR AMOUNT OF WIRE'S WITHIN. 3) PROVIDE TWO POINTS OF PIPE SUPPORT FOR RISER PER TOP ( PROVIDE BLOCKING IN WALL FOR STRAPS) 4) MAST HEAD OVER 24" REQUIRES GUY WIRES PER T.E.P. |