Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T12CM08013
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2013 | BUILDING - PROGRESS | Approved | ||
01/11/2013 | BUILDING - PROGRESS | Partial Approval | Met with contractor on site. There are large areas of structural beams where the firesafing had been removed for a remodel some decades in the past. This condition is unsafe and must be remidied. 2 hour construction required for floor beams and 1.5 hour required for roof beams. |