Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/12/2013 | BUILDING - FINAL | Denied | 125 AMP MAIN TO BIG IN SERVICE NOT PER PLAN PLAN CALLS FOR 100 AMP MAIN DISCONNECT |
|
| 06/05/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/05/2013 | BUILDING - FINAL | Denied | 125 MAINS X 120% = PV BREAKER 25 AMP. YOU HAVE A 40 AMP. TALK TO ENGINEER ABOUT A SERVICE UPGRADE OR HOW TO RESOLVE THIS PROBLEM. | |
| 05/29/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/29/2013 | BUILDING - FINAL | Denied | WRONG SIZE BREAKER FOR PV IN SERVICE PANEL ROOF OK |