Permit: T12CM07960

Parcel: 10408095C

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T12CM07960

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2016 FIRE - ALARM FINAL Approved
08/16/2016 FIRE - ALARM FINAL Denied 1) Placement of HVLS fans (pushing over 2000 cfm) over vehicle pick up/drop off area now requires fans to be automatically shut down upon waterflow or smoke/heat detection and for signal to be sent to the fire alarm panel.
2) All duct detectors must have test and balance sheet available to the inspector and with such 10% or more of the duct detectors will be tested.