Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12CM07960
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2016 | FIRE - ALARM FINAL | Approved | ||
| 08/16/2016 | FIRE - ALARM FINAL | Denied | 1) Placement of HVLS fans (pushing over 2000 cfm) over vehicle pick up/drop off area now requires fans to be automatically shut down upon waterflow or smoke/heat detection and for signal to be sent to the fire alarm panel. 2) All duct detectors must have test and balance sheet available to the inspector and with such 10% or more of the duct detectors will be tested. |