Permit: T12CM07744

Parcel: 11706245C


Addresses:

202 E 12TH ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM07744

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2013 FIRE - FINAL Approved MUST COMPLY WITH NOTES FROM CBASALDUA
10/11/2013 FIRE - FINAL Partial Approval 1. Okay for Temporary Certificate of Occupancy.
2. Need to add smoke detector above F.A.C.P.
10/10/2013 FIRE - FINAL Partial Approval 1. Okay for TCO.
2. All doors need to be self latching.
3. Alarm system needs to be reset and active.
4. See fire alarm notes.
5. Lock Box being ordered.
09/19/2013 FIRE - FINAL Denied 1. Fire extinguishers need service.
2. Sprinkler system needs annual service.
3. Alarm system needs to be in service.
4. Need plans and permits for all suppression system work.