Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2013 | ELECTRIC - FINAL | Approved | Century link shows that pedistal has been at that location since time of original construction. Pedistal does sit within clear work space, but based on previous approvals for location, the capability for work to still be done safely on the new service, and that it would cost homowner $3800 to relocate it, I am accepting this installation. | |
| 01/11/2013 | ELECTRIC - FINAL | Partial Approval | NEED TO SEE PAPERWORK FROM CENTURY LINK ABOUT PEDISTAL. | |
| 01/09/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/08/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DEAD FRONT WILL NOT FIT BACK ON DUE TO 2 1/2" HUB TO FAR FRONT OF TOP OF SERVICE PANEL |