Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T12CM07724
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2013 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/16/2013 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/08/2013 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
04/08/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/08/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | 1) PROVIDE PHYSICAL PROTECTION OF LIFE SAFETY CIRCUIT 517.30 (C)(3) 2) NEED SUPPORT WIRE FOR EXIT LIGHTS 3) SUPPORT DATA RUNS 725.24, 760.24, 800.24, 300.11 4) SUPPORT M/C & WHIPS 300.11 |