Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T12CM07677
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2012 | PLUMBING - FINAL | Not ready for Inspection | 1. No new piping. Blk iron pipe may not be installed under the building, but must be kept at least 6" above grade or structure. At the water heater: Flex may not pass thru the water heater partition. Require approved valves. No T&P relief drain. Shut off valve at cold inlet to be accessible. Unable to locate the bond between the gas and the water. No plan on site. Unable to make review. |