Permit: T12CM07652

Parcel: 122050540


Addresses:

4345 E EDISON ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/30/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/16/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
Provide an approved hole seal to fill knockout on side of panel. Screw holes also need to be sealed with bolts and washers. Provide the required structural drawing
12/13/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BLOCK AND CLAMP PVC EVERY 4' A/C UNIT IS OVERFUSED ELEC. PANEL DEAD FRONT HAS BEEN ALTERED FOR A/C CIRCUIT CONDUIT. REPLACE DAMAGED DEAD FRONT AND CONNECT CONDUIT TO A KNOCKOUT PROVIDED BY THE MANUFACTURER. PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON ROOF.