Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : Provide an approved hole seal to fill knockout on side of panel. Screw holes also need to be sealed with bolts and washers. Provide the required structural drawing |
|
| 12/13/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BLOCK AND CLAMP PVC EVERY 4' A/C UNIT IS OVERFUSED ELEC. PANEL DEAD FRONT HAS BEEN ALTERED FOR A/C CIRCUIT CONDUIT. REPLACE DAMAGED DEAD FRONT AND CONNECT CONDUIT TO A KNOCKOUT PROVIDED BY THE MANUFACTURER. PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON ROOF. |