Permit: T12CM07650

Parcel: 11803297Q


Addresses:

1609 S FICKETT AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T12CM07650

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/11/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/07/2012 MECHANICAL - FINAL Denied 1) ROMEX SHEATH TO EXTEND 1/4" INTO ENCLOSURE USE APPROVED CABLE CLAMP. ALSO CABLE OBSTRUCTS PROPER DOOR CLOSURE
2) UNIT HAS 60 AMP CIRCUIT BREAKER, PANEL HAS 90 AMP-
3) VERIFY WIRE SIZE FOR OVER CURRENT PROTECTION