Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/22/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/09/2013 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
01/07/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE BOND BUSHING ON 1 1/2" LB AT PANEL TERMINATION.
2. LOCK NUT INSIDE OR OUTSIDE OF CHASE NIPPLE 2 1/2" TO PROVIDE A RELIABLEMECH & GROUND CONNECTION TO ENCLOSURE.
3.PHASE WHITE WIRE USED AS HOT
4. SUPPORT OR STRAP #4 BARE TO STRUCTURE
5. #6 ROMEX TO SMALL FOR 100 AMP CIRCUIT BREAKER
6. PROVIDE BACKING UNDER CONDUIT (2 1/2 ") AT TOP STRAP
7. GROUND ROD IN FRONT OF SERVICE PANEL IS A TRIP HAZARD