Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/09/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/07/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE BOND BUSHING ON 1 1/2" LB AT PANEL TERMINATION. 2. LOCK NUT INSIDE OR OUTSIDE OF CHASE NIPPLE 2 1/2" TO PROVIDE A RELIABLEMECH & GROUND CONNECTION TO ENCLOSURE. 3.PHASE WHITE WIRE USED AS HOT 4. SUPPORT OR STRAP #4 BARE TO STRUCTURE 5. #6 ROMEX TO SMALL FOR 100 AMP CIRCUIT BREAKER 6. PROVIDE BACKING UNDER CONDUIT (2 1/2 ") AT TOP STRAP 7. GROUND ROD IN FRONT OF SERVICE PANEL IS A TRIP HAZARD |