Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/03/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/03/2013 | ELECTRIC - FINAL | Partial Approval | LABEL ALL BREAKERS | |
| 05/01/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/30/2013 | ELECTRIC - FINAL | Partial Approval | OK FOR FINAL AFTER CROSSOVER OF ATM | |
| 04/29/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/29/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/29/2013 | ELECTRIC - FINAL | Partial Approval | 1) SUPPORT VDV CABLEING 725.3 800.3, 725.8, 800.24, 300.11- NOT OFF OF OTHER WIRING METHODS- TEMP WIRING 2) LABEL ALL BREAKERS 408.4 3) CHARGE EM AND EXITS TO VERIFY WORKING AND CIRCUITRY 4) NEED TO SEE NEW ATM TO VERIFY LISTING |