Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM07499

Parcel: 13612001P

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T12CM07499

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2013 FIRE - ALARM FINAL Approved
10/23/2013 FIRE - ALARM FINAL Denied 1. Duct smoke failed to shut down A/C units
2. By front door bad pull station
3. Need lock on breaker to the FACP
4. Need a UL/FM cert. for monitoring set to the fire department.
5. Need plans to that show changes were made, according to the plans system was to be wired as a class "A" system but only the storbes are and not the pull stations, will need to cahnge the plans or wire per approved plans.