Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2013 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Approved |
|
| 05/30/2013 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Okay to bury - Need 200 psi for 2 hours and flush - for flushing can not be smaller than 4 inch and hooked to the city line. |
| 05/24/2013 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Denied |
1. need seperate plans and permit as stated on approved plans stamped by fire. |