Permit: T12CM07499

Parcel: 13612001P

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T12CM07499

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2013 FIRE SPKLR - UG, PIPING, HYDRO Approved
05/30/2013 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Okay to bury - Need 200 psi for 2 hours and flush - for flushing can not be smaller than 4 inch and hooked to the city line.
05/24/2013 FIRE SPKLR - UG, PIPING, HYDRO Denied 1. need seperate plans and permit as stated on approved plans stamped by fire.